29
Group 08 Protection Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
08-25
Detection
selection of
External
Fault
0: Immediately
Detect when
the Power is
Supplied.
0
1: Start to
Detect during
Operation
08-26
~
08-29
Reserved
08-30
Selection of
Run
Permissive
Function
0: Deceleration
to Stop
0
1: Coast to
Stop
08-31
~
08-34
Reserved
08-35
Fault
Selection of
Motor
Overheat
0: Disable
0
1: Deceleration
to Stop
2: Coast to
Stop
08-36
Time
Coefficient
of PTC
Input Filter
0.00 ~ 5.00 2
08-37
Fan Control
Function
(Note)
0: Start at
Operation
0
1: Permanent
Start
2: Start at High
Temperature
08-38
Delay Time
of Fan Off
0~600 60
08-39
Delay Time
of Motor
Overheat
Protection
1~300 60
08-42
PTC Trip
Level
0.1~10.0 0.7
Note1
08-43
PTC Reset
Level
0.1~10.0 0.3
Note1
08-45
PTC
Disconnectio
n Detection
0: Disable
0
Note3
1: Warning
2: Fault
08-46
Over-
temperature
Protection
Level
0~254°C 0
Note6
08-47
Over-
temperature
Reset Level
0~254°C 0
Note6
08-48
Fire Mode
Selection
0: Disable
1: Enable
0
Note6
08-49
Fire Mode
Digital Input
Type
0: Power Loss
Reset
1: Terminal
Removal Reset
0
Note6
08-50
Fire Mode
Digital
XXX0b: S6 A
contact
0000b
Note6
Group 08 Protection Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
Terminal
Status
XXX1b: S6 B
contact
08-51
Fire Mode
Motor
Speed
Selection
0: Fire Mode
Operation
1: PID
Frequency
Command
2: AI2
Frequency
Command
0
Note6
08-52
Fire Mode
Motor
Speed
0.00~100.00 100.00
Note6
08-53
Fire Mode
PID
Detection
Level
0~100 0
Note6
08-54
Fire Mode
PID
Disconnecti
on Delay
0.0~10.0 1.0
Note6
08-55
Fire Mode
PID
Disconnecti
on
Selection
0: Current
Speed
1: Fire Mode
Speed (08-52)
2: Motor 1
Maximum
Frequency (01-
02)
1
Note6
08-56
Fire Mode
AI2
Detection
Level
0.0~100.0 80.0
Note6
08-57
Fire Mode
AI2
Disconnecti
on Delay
0.0~10.0 1.0
Note6
08-58
Fire Mode
AI2
Disconnecti
on Selection
0: Current
Speed
1: Fire Mode
Speed (08-52)
2: Motor 1
Maximum
Frequency (01-
02)
1
Note6
08-59
Fire Mode
Motor
Direction
0: Forward
Direction
1: Reverse
Direction
0
Note6
08-60
Fire Mode
Password
00000~65534 0
Note6
Note: Standard H & C type models of inverter
ratings for 2060 and 4100 above in IP20 enclosure
do not have this function. Enhanced E & G type
models of inverter for 2060 and 4100 above in IP20
enclosure do not have “Start at high temperature”
function.