30
Group 09: Communication Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
09-00
INV
Communica
tion Station
Address
1~31 1
*2
*3
09-01
Communica
tion Mode
Selection
0: MODBUS
0 *3
1: BACNET
2: METASYS
3: PUMP in
Parallel
Connection
09-02
Baud Rate
Setting
(bps)
0:1200
4
*2
*3
*6
1:2400
2:4800
3:9600
4:19200
5:38400
09-03
Stop Bit
Selection
0:1 Stop Bit
0
*2
*3
1: 2 Stop Bit
09-04
Parity
Selection
0: No Parity
0
*2
*3
1: Even Bit
2: Odd Bit
09-05
Communica
tions Data
Bits
Selection
0: 8 bits data
0
*3
Note1
1: 7 bits data
09-06
Communica
tion Error
Detection
Time
0.0~25.5 0.0 *3
09-07
Fault Stop
Selection
0: Deceleration
to Stop Based
on Deceleration
Time 1 when
Communication
Fault Occurs.
3 *3
1: Coast to
Stop when
Communication
Fault Occurs.
2: Deceleration
to Stop Based
on Deceleration
Time 2 when
Communication
Fault Occurs.
3: Keep
Operating
when
Communication
Fault Occurs.
4: Run the
Frequency
Command
given by AI2
09-08
Comm.
Fault
Tolerance
Count
1~20 1 *3
09-09 Waiting 5~65 5 *3
Group 09: Communication Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
Time
09-10
Device
Instance
Number
1 ~ 254 1 *3
*3: Parameters in group 09 are not affected by
parameter 13-08 (initialization).
Group 10: PID Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
10-00
PID Target
Value
Source
Setting
0: PUMP or
HVAC
function
given (refer
to group 23)
1
1: AI1 Given
2: AI2 Given
3: Reserved
4: 10-02 Given
5: Reserved
Note
6: Frequency
Command
(00-05)
Note
7: Multi-speed
Frequency
Command
10-01
PID
Feedback
Value
Source
Setting
1: AI1 Given
2
2: AI2 Given
3: Reserved
4: AI1 - AI2
Given
10-02
PID Target
Value
0.0~100.0 0.0
10-03
PID Control
Mode
xxx0b: PID
Disable
0000b
xxx1b: PID
Enable
xx0xb: PID
Positive
Characteristic
xx1xb: PID
Negative
Characteristic
x0xxb: PID
Error Value of
D Control
x1xxb: PID
Feedback
Value of D
Control
0xxxb: PID
Output
1xxxb: PID
Output +
Frequency
Command
10-04
Feedback
Gain
0.01~10.00 1.00 *1

Other manuals for TECO F510 series