31
Group 10: PID Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
10-05
Proportional
Gain (P)
0.00~10.00 3.00 *1
10-06
Integral
Time (I)
0.00~100.00 0.50 *1
10-07
Differential
Time (D)
0.00~10.00 0.00 *1
10-08 Reserved
10-09 PID Bias -100.0~100.0 0 *1
10-10
PID Primary
Delay Time
0.00~10.00 0.00 *1
10-11
PID
Feedback
Loss
Detection
Selection
0: Disable
0
1: Warning
2: Fault
10-12
PID
Feedback
Loss
Detection
Level
0~100 0
10-13
PID
Feedback
Loss
Detection
Time
0.0~10.0 1.0
10-14
PID Integral
Limit
0.0~100.0 100.0 *1
10-15
10-16
Reserved
10-17
Start
Frequency
of PID
Sleep
0.00~599.00
(Note8)
30.00
10-18
Delay Time
of PID
Sleep
0.0~255.5 0.0
10-19
Frequency
of PID
Waking up
0.00~599.00
(Note8)
0.00
10-20
Delay Time
of PID
Waking up
0.0~255.5 0.0
10-21
10-22
Reserved
10-23 PID Limit 0.00~100.0 100.0 *1
10-24
PID Output
Gain
0.0~25.0 1.0
10-25
PID
Reversal
Output
Selection
0: Do not Allow
Reversal
Output
0
1: Allow
Reversal
Output
10-26
PID Target
A
cceleration/
Deceleration
Time
0.0~25.5 0.0
10-27
PID
Feedback
Display Bias
0~9999 0
Group 10: PID Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
10-28 Reserved
10-29
PID Sleep
Selection
0: Disable
1 1: Enable
2: Set by DI
10-30
Upper Limit
of PID
Target
0.0 ~ 100.0 100.0
10-31
Lower Limit
of PID
Target
0.0 ~ 100.0 0.0
10-32
PID
Switching
Function
0: PID1
0
1: PID2
2: Set by DI
3: Switch to
PID2 when
RTC Timer
Enables
10-33
PID
Maximum
Feedback
Value
1~10000 999
10-34
PID Decimal
Width
0~4 1
10-35 PID Unit
0: %
0 *6
1: FPM
2: CFM
3: PSI
4: GPH
5: GPM
6: IN
7: FT
8: /s
9: /m
10: /h
11: °F
12: inW
13: HP
14: m/s
15: MPM
16: CMM
17: W
18: KW
19: m
20: °C
21: RPM
22: Bar
23: Pa
24: KPa
Note4
10-36
PID2
Proportional
Gain (P)
0.00~10.00 3.00 *1
10-37
PID2
Integral
Time (I)
0.0~100.0 0.50 *1
10-38
PID2
Differential
Time (D)
0.00~10.00 0.00 *1
10-39
PID Output
Frequency
00.00~599.00
(Note8)
30.00 *6