EasyManua.ls Logo

TECO F510 series - 3.3 Inverter Wiring

TECO F510 series
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
32
Group 10: PID Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
Setting during
disconnection
10-40
Compensatio
n Frequency
Selection of
PID Sleep
0: Disable
0
Note1
1: Enable
10-41
~
10-43
Reserved
10-44
Precharge
Frequency
0.0~120.0 0
Note3
10-45
Precharge
Time
0~250 0
Note3
10-46
Precharge
Target Level
0~10000 0
Note3
10-47
Proportional
Gain 3(P)
0.00~10.00
3.00
Note6
10-48
Integral
Time 3(I)
0.00~100.00
0.50
Note6
10-49
Differential
Time 3(D)
0.00~10.00
0.00
Note6
Group 11: Auxiliary Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
11-00
Direction
Lock
Selection
0: Allow
Forward and
Reverse
Rotation
1
1: Only Allow
Forward
Rotation
2: Only Allow
Reverse
Rotation
11-01
Carrier
Frequency
0: Carrier
Output
Frequency
Tuning
Inverter
KVA
*a
1: 1~16:
1~16KHz
11-02
Soft PWM
Function
Selection
0: Disable
1
*
b
1: Soft PWM
Function 1
2: Soft PWM
Function 2
11-03
Automatic
carrier
lowering
selection
0: Disable
0
1: Enable
11-04
S-curve
Time
Setting at
the Start of
Acceleration
0.00~2.50 0.20
11-05
S-curve
Time
0.00~2.50 0.20
Group 11: Auxiliary Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
Setting at
the End of
Acceleration
11-06
S-curve Time
Setting at the
Start of
Deceleration
0.00~2.50 0.20
11-07
S-curve Time
Setting at the
End of
Deceleration
0.00~2.50 0.20
11-08
Jump
Frequency 1
0.0~599.00
(Note8)
0.0
11-09
Jump
Frequency 2
0.0~599.00
(Note8)
0.0
11-10
Jump
Frequency 3
0.0~599.00
(Note8)
0.0
11-11
Jump
Frequency
Width
0.0~25.5 1.0
11-12
Manual
Energy
Saving Gain
0~100 80
11-13
Automatic
Return Time
0~120 60 *6
11-14
~
11-17
Reserved
11-18
Manual
Energy
Saving
Frequency
0.00~599.00
(Note8)
0.00
11-19
Automatic
Energy
Saving
Function
0: Disabled
0
1: Enabled
11-20
Filter Time
of Automatic
Energy
Saving
0~200 140
11-21
Voltage
Upper Limit
of Energy
Saving
Tuning
0~100 100
11-22
Adjustment
Time of
Automatic
Energy
Saving
0~5000 20 *1
11-23
Detection
Level of
Automatic
Energy
Saving
0~100 10
11-24
Coefficient
of Automatic
Energy
Saving
0.00~655.34 KVA
*a

Other manuals for TECO F510 series