37
Group 12: Monitoring Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
12-55
Output
Frequency
of Previous
Fault
Display output
frequency of
previous fault
-
12-56
Output
Current of
Previous
Fault
Display output
current of
previous fault
-
12-57
Output
Voltage of
Previous
Fault
Display output
voltage of
previous fault
-
12-58
DC Voltage
of Previous
Fault
Display DC
voltage of
previous fault
-
12-59
DIO Status
of Previous
Fault
Display DI/DO
status of
previous fault
Description is
similar to 12-05
-
12-60
Inverter
Status of
Previous
Fault
Display inverter
status of
previous fault
Description is
similar to 12-43
-
12-61
Trip time 1
of last fault
Display the
operation time
of last time’s
fault, 12-62 is
the days, while
12-61 is the
remaining
hours.
-
12-62
Trip time 2
of last fault
-
12-63
Recent
warning
messages
Display the
recent warning
messages
-
12-64
Previous
warning
message
Display the
previous
warning
message
-
12-65
~
12-66
Reserved
12-67
Accumulativ
e Energy
(kWHr)
0.0 ~ 999.9
12-68
Accumulativ
e Energy
(MWHr)
0 ~ 60000
12-69
Accumulativ
e Electricity
Price ($)
0 ~ 9999
12-70
Accumulativ
e Electricity
Price
(10000$)
0 ~ 60000
12-71
Flow Meter
Feedback
1 ~ 50000
12-72 RTC Date
12.01.01 ~
99.12.31
12.01.01
Group 12: Monitoring Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
12-73 RTC Time 00:00 ~ 23:59 00:00
12-74
Operating
Pressure
Setting
0.01 ~ 25.50 2.00
12-75
Pressure
Feedback
Value
0.01 ~ 25.50 -
12-76
Non-Load
Voltage
0.0 ~ 600.0 -
12-77
Flow Meter
Target
Setting
1 ~ 50000 - *7
12-78 Reserved
12-79
Pulse Input
Percentage
0.0~100.0 - *7
12-81
Relay Card
Display
ON: LCD
display is 1
OFF: LCD
display is 0
-
Note5
12-82 Motor Load 0 ~ 200.0 -
Note6
12-85 AI3 Input
Display the
current Al3 input
(-10V
corresponds to -
100%, 10V
corresponds to
100%)
- *10
* Models of inverter ratings above 200V 60HP
(including 60HP) and 400V 100HP (including
100HP) in IP20 enclosure do not support
functions of heatsink temperature display. All
models in IP55 enclosure support functions of
heatsink temperature display.
* Maximum upper limit in motor speed (rpm) of
parameter 12-22 is 65534.
Group 13 Maintenance Function Group
Code
Parameter
Name
Setting Range Default
Attribu
te
13-00
Inverter
Rating
Selection
00H~FFH - *4
13-01
Software
Version
0.00-9.99 - *4
13-02
Clear
Cumulative
Operation
Hours
Function
0: Disable to
Clear
Cumulative
Operation
Hours
1: Clear
Cumulative
Operation
Hours
0
*1
13-03
Cumulative
Operation
Hours 1
0~23 - *4
13-04
Cumulative
Operation
Hours 2
0~65534 - *4

Other manuals for TECO F510 series