36
Group 12: Monitoring Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
12-30
~
12-35
Reserved
12-36 PID Input
Display input
error of the PID
controller (PID
target value - PID
feedback)
(100%
corresponds to
the maximum
frequency set by
01-02 or 01-16)
-
12-37 PID Output
Display output of
the PID controller
(100%
corresponds to
the maximum
frequency set by
01-02 or 01-16)
-
12-38 PID Setting
Display the target
value of the PID
controller (100%
corresponds to
the maximum
frequency set by
01-02 or 01-16)
-
12-39
PID
Feedback
Display the
feedback value
of the PID
controller
(100%
corresponds to
the maximum
frequency set by
01-02 or 01-16)
-
12-40 Reserved
12-41
Heatsink
Temperatur
e
Display the
heatsink
temperature of
IGBT
temperature.
-
12-42
RS-485
Error Code
LCD Display:
0000 0000
1: CRC Error
1 : D ata le n g th E rro r
1: Data Function E rror
1: P arity E rro r
1: O verrun E rror
1: Framing Error
1: Time Out Error
Reserved
LED Display:
(without any
error)
LED Display:
(with certain
error)
1: CRC Err or
1: Data length Error
1: Data Function Error
1: P arit y Er ror
1: Framing Er ror
1: Time out Error
Reserv ed
1: Overrun Error
- *7
12-43
Inverter
Status
LCD Display: 101B
Group 12: Monitoring Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
0000 0000
1: I nvert er ready
1: During runni ng
1: During zero speed
1: During speed agree
1: Duri ng faul t detecti on
(minor faul t)
1: Duri ng faul t detecti on
(major faul t)
Reser v ed
LED Display:
Inverter ready
1
Running 2
Zero Speed 4
Frequenc
y
A
g
ree 8
Warning 16
Error 32
Inverter status
display is the
summed up
value. Ex:
Display of the
value 6 means
the inverter is
running in zero
speed.
12-44 Reserved
12-45
Recent
Fault
Message
Display current
fault message
-
12-46
Previous
Fault
Message
Display
previous fault
message
-
12-47
Previous
Two Fault
Messages
Display
previous two
fault messages
-
12-48
Previous
Three Fault
Messages
Display
previous three
fault messages
-
12-49
Previous
Four Fault
Messages
Display
previous four
fault messages
-
12-50
DIO Status
of Current
Fault
Display the
DI/DO status of
current fault
Description is
similar to 12-05
-
12-51
Inverter
Status of
Current
Fault
Display the
inverter status
of current fault
Description is
similar to 12-43
-
12-52
Trip Time 1
of Current
Fault
Display the
operation time
of current fault,
12-53 is the
days, while 12-
52 is the
remaining
hours.
-
12-53
Trip Time 2
of Current
Fault
-
12-54
Frequency
Command
of Previous
Fault
Display
frequency
command of
previous fault
-

Other manuals for TECO F510 series