EasyManua.ls Logo

TECO F510 series - 3.3.3 General Wiring Diagram

TECO F510 series
108 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
35
Group 12: Monitoring Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
Display at Two
Decimal Places.
(xxx.xx)
4: Line Speed
Display at Three
Decimal Places.
(xx.xxx)
12-05
Status
display of
digital input
terminal
(LED / LCD)
LED display is
shown as
below no input
correspondenc
es to input
andoutput
LCD display is
shown as
below
0000 0000
Input Terminal(S6)
Input Terminal(S5)
Input Terminal(S4)
Input Terminal(S3)
Input Terminal(S2)
Input Terminal(S1)
0:OPEN
1:CLOSE
0
Output Terminal(R3)
Output Terminal(R2)
Output Terminal(R1)
-
12-06
~
12-10
Reserved
12-11
Output
Current of
Current
Fault
Display the
output current
of current fault
-
12-12
Output
Voltage of
Current
Fault
Display the
output voltage
of current fault
-
12-13
Output
Frequency
of Current
Fault
Display the
output
frequency of
current fault
-
12-14
DC Voltage
of Current
Fault
Display the DC
voltage of
current fault
-
12-15
Frequency
Command
of Current
Fault
Display the
frequency
command of
current fault
-
12-16
Frequency
Command
If LED enters this
parameter, it only
allows monitoring
frequency
command.
-
12-17
Output
Frequency
Display the
current output
frequency
-
12-18
Output
Current
Display the
current output
-
Group 12: Monitoring Parameters
Code
Parameter
Name
Setting Range Default
Attribu
te
current
12-19
Output
Voltage
Display the
current output
voltage
-
12-20 DC Voltage
Display the
current DC
voltage
-
12-21
Output
Power
Display the
current output
power
-
12-22
Motor’s
Rotation
Speed
Display motor’s
current rotation
speed
in VF/SLV mode
Motor’s rotation
speed = output
power
x(120/motor’s
pole number)
In PG/SV mode,
motor’s rotation
speed is
calculated by
feedback
frequency.
Max limit is
65535
-
12-23
Output
Power
Factor
Display the
current output
power factor
-
12-24
Control
Mode
Display control
mode
0 : VF
2 : SLV
5 : PM SLV
-
12-25 AI1 Input
Display the
current Al1 input
(0V corresponds
to 0%, 10V
corresponds to
100%,)
-
12-26 AI2 Input
Display the
current Al2
input
(0V or 4mA
corresponds to
0%, 10V or
20mA
corresponds to
100%)
-
12-27
Motor
Torque
Display the
current torque
command
(100%
corresponds to
motor torque )
-
12-28
Motor
Torque
Current (Iq)
Display the
current q-axis
current
-
12-29
Motor
Excitation
Current (Id)
Display the
current d-axis
current
-

Other manuals for TECO F510 series