EasyManua.ls Logo

TECO SG2-20VR-D - Page 170

TECO SG2-20VR-D
270 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 6 FBD Block Diagram Programming 162
(6) Counter Mode 5 (Continuous Count, Up-Down Count, Non-Retentive)
Mode 5 Counters operation is similar to Mode 2 except its current count value is continuous and non-retentive. The status bit
is fixed to the non-zero preset value regardless of the state of the direction bit. Its status bit will be ON when the counter current
value isn’t less than its preset value, and will be OFF when the current value is less than its preset value.
FBD display Parameter display
Counting Input
Up/Down Counting
Current value
Reset
Preset value
Counting Parameter
Note: The “C” means compare count;
The “>”means the current value appeared will be greater than present value.
Under this mode, the count will continuous after reaching its preset value;
The current value is always 0 regardless of the state of its direction bit when the reset is availability;
The current value is always 0 regardless of the state of its direction bit when the smart switches between RUN and
STOP.
PDF compression, OCR, web optimization using a watermarked evaluation copy of CVISION PDFCompressor

Table of Contents

Other manuals for TECO SG2-20VR-D

Related product manuals