Chapter 9 Expansion Module 231
Connect with electrical source
Input 24VDC
NSMS
+
-
①-1A quick-blowing fuse, circuit-breaker or circuit protector.
②-Surge absorber.
Connect with DeviceNet network
Using 5-pin network tie-in connected DNET to DeviceNet bus. Please use network tie-in and cable ordained by
ODVA. The style of cable decides the maximal length of cable and baud rate of communication at more degree.
1: GND black
2: CAN_L blue
3: Shield no color
4: CAN_H white
5: 24V red
Address and Baud rate set
In equipment network, each slave node needs a difference MAC ID, and the maximal number of ID is 64 (0~63).
The address of node can be set by SW1-1~SW1-6 of DNET oneself mode. And the baud rate of communication can
be set by SW1-7 and SW1-8, the baud rate set must be the same as equipment network.
SW1_1~SW1_6: ID in network
SW1-1 SW1-2 SW1-3 SW1-4 SW1-5 SW1-6 ID
OFF OFF OFF OFF OFF OFF 0
ON OFF OFF OFF OFF OFF 1
OFF ON OFF OFF OFF OFF 2
ON ON OFF OFF OFF OFF 3
OFF OFF ON OFF OFF OFF 4
┈ ┈ ┈ ┈ ┈ ┈ ┈
OFF ON ON ON ON ON 62
ON ON ON ON ON ON 63