35 
 
 
 
F_06: frequency upper limit range=1~120Hz 
F_07: frequency lower limit range=1~120Hz 
(1~200Hz with CPU versionv1.9 and above) 
F_06: Factory setting refers to F_25. 
 
 
 
 
 
 
 
 
NOTE: 
If F_07 = 0 Hz,  If the frequency instruction is equal to 0Hz, the inverter will  
    stop at 0 speed. 
If F_07 > 0 Hz,   If the  frequency instruction is lower than F_07, the inverter will  
       output a minimum speed according to the setting in F_07 
 
F_08: SP1 frequency = 1 ~ 120Hz(1~200Hz:CPU version v1.9 and above)
F_09: JOG frequency = 1 ~ 120Hz(1~200Hz:CPU version v1.9 and above)
1.  When F_19 or F_20 = 2 and the multifunction input terminal is ON, the inverter operates at sp1 
frequency (F_08) 
2.  When F_19 or F_20 = 1 and the multifunction input terminal is ON, the inverter operate at jog 
frequency (F_09) 
3.  The priority of reading frequency setting is: Jog→ Sp1→Keypad setting or external frequency 
signal using a speed pot. 
 
F_10: Start / Stop Control  
= 0: Keypad  
= 1: Terminal (TM2) 
NOTE: When F_10=1 (Terminal Control), emergency stop on the Keypad is enabled. 
When F_10=1, please refer to the descriptions of F_23/24, in order to avoid the damage to the 
human and the machine. 
 
 
 
 
 
 
 
 
 
 
 
 
 
Internal 
frequency 
signal 
(NOTE) 
Frequency setting signal 
F_06 (freq. Upper limit) 
F_07 (freq. Lower limit) 
Time 
Hz 
F_10=1 
      or =0 
F_09=10Hz 
F_19=1 
F_08=30Hz 
F_20=2 
ON OFF 
OFF 
ON OFF 
ON
OFF 
OFF ON 
OFF