56 
 
 
 
Maintenance and Examination 
 
Frequent examination and maintenance is not required for the inverter. 
To maintain appropriate reliability, please proceed with following periodical examination. Remember to 
turn off power supply and wait till the Power LED goes off before proceed. (Due to the large amount of 
remaining charges in the internal capacitors.) 
 
 
(1)  Clean out internal dust and dirt. 
(2)  Check out mounting screws on every terminal and parts. Tighten loose screws. 
(3) Dielectric strength test 
 
(a)  Remove all conducting wires between Drive and outside world. Power must be turned OFF. 
(b)  The dielectric strength test inside Drive should be carried out only for T-VERTER major circuitry. Use 
DC 500V: high resistance meter. Measured resistance should be higher than 100M ohm. 
 
 
CAUTION: Do not perform dielectric strength test to the control circuit. 
 
 
 
 
 
Connection for dielectric strength test 
 
Input power source 
DC-500V 
high-resistance 
meter 
Grounding terminal
 
Motor 
L1 (R)        T1 (U)
 
L2 (S)  Drive    T2 (V) 
 
  T3 (W)