NOTE: When F_13 = 0, the torque boost function is disabled. 
 
F_14 Stopping method        = 0 : Controlled deceleration stop
  = 1 : free run to stop 
F_15 DC braking time             = 0 ~ 25.5 sec 
F_16 DC braking starting frequency  = 1 ~ 10 Hz 
F_17 DC braking level         = 0 ~ 20 % 
 
If F_14 = 0 
When the inverter receives the stop command, it decelerate to the pre-set frequency setup by F_16 after 
this the output voltage level that is set in the F_17; will determine the amount of DC voltage that’s 
injected into the motor.  The time duration to perform this stopping function is setup in F_15.  
 
 
 
 
 
 
 
 
 
 
 
If F_14 = 1 
The inverter stops output immediately after receiving the stop command. The motor will enter into a free 
running state until it comes to a complete stop. 
1 2.5/3.0 
50/60 
Hz 
F_13= 
B 
C 
100% 
Voltage 
Run Command 
Output Frequent  Deceleration Time 
DC Braking Frequency 
DC Braking Time