Betriebsanleitung/Operating manual
EGS80X002001
28 BD_BE 987 b www.tecsis.de
4.2 Connection
The detachable clamps of the EGS80
considerably simplify the connection
and the switch cabinet assembly. They
make it possible to replace devices
quickly and without error if a customer
service becomes necessary.
Terminals are equipped with screws,
are self-opening, have a large
connection area for a wire cross-
section up to 2.5 mm² and coded
plugs, making it impossible to mix them up.
Terminals 1 through 3 of the EGS80 are used for the field current circuit
connection.
You can connect:
• a 3-wire transmitter
• a 2-wire transmitter
• an active source
The remaining terminals have the following functions:
• Terminals 7/8: power out (9 unused)
• Terminals 10 ... 12: relay 1
• Terminals 16 ... 18: relay 2
• Terminals 23/24: power supply (22 unused)
Terminals 4 ... 6, 13 ... 15 and 19 ... 21 are not present on the EGS80.
3