Betriebsanleitung/Operating manual
EGS80X002001
www.tecsis.de BD_BE 987 b 35
6.3 Input
The following illustration shows the menus for the input parameters.
Menu options on the lowest level are outlined in bold. The menu items
Zero point and Conversion factor will not be shown if the unit mA is
selected (section 6.2).
6.3.1 Line monitor
• If you select ON for LB, an input current < 0.2 mA will be registered
as a lead break/open circuit (see section 5).
• If you select ON for LK, an input current > 22 mA will be registered as
a short circuit (see section 5).
If you wish to process the 0.2 mA input values as measured values,
you must deselect the lead breakage detection (Off LB). If not, an error
will be signalled within the measuring range.