Betriebsanleitung/Operating manual
EGS80X002001
38 BD_BE 987 b www.tecsis.de
6.4.1 Operating behavior
For switching mode, Max or Min can be selected; as operating mode
you can select Active or Passive (see section 6.4).
Areas of Application:
• Switching mode MAX, operating mode Active:
alarm on over range, for instance audible alarm
• Switching mode MAX, operating mode Passive:
overfill protection, for instance, turn off pump;
for large hysteresis MIN-MAX operation, for instance pump on/off
• Switching mode MIN, operating mode Active:
alarm on under range, for instance audible alarm
• Switching mode MIN, operating mode Passive:
overload protections, for instance switching off a pump if nothing is
flowing.
The exact switching behaviour of the EGS80 is shown in the following
illustration: