Mode Item Field Range Access Description
1
2
3
4
OFF, On
Default = On
InST
ADV
RELAY 1 PUMP
SECTION L
Select whether a system pump from a tN4 system control
should operate whenever relay 1 is closed.
Note: This item is only available when DIP switch 2 is set
to tN4 System Control, and the Heat Source item in the
ADJUST menu is set to hydronic (HYDr).
1
2
4
OFF, 1 to 12
Default = 1
ADV
SETPOINT DEVICE ENABLE SECTION E
Select the Setpoint Device Enable number to allow a
remote device such as a User Switch to activate the Time
Occupied override. The control then maintains the occupied
temperature for a preset amount of time.
Note:
This item is only available when the setpoint control
has tN4 communication.
After the last item, the control returns to the first item in the menu.
ADJUST Menu (5 of 5)