www.temcoline.com
DIGITAL PID CONTROLLER
5. Ratings and Specifications
T30-SERIES
Model
Power supply
Power consumption
Display Accuracy
Control
Output
Alarm
output
ALARM 1, 2
(LBA common)
Relay
Voltage
(S.S.R)
Current
(S.C.R)
Input Impedance
Input sampling period
Control Method
Multi SV Input (D.I)
Retransmission Output
Ambient temperature
and Humidity
Weight
(Bracket, Accessories included)
Input Type
5VA (Max.)
±0.3% of FS +1 Digit
50~250ms (variable according to SG-PID algorithm)
DC15V 25mA (built-in short protection circuit)
Voltage pulse (time proportional PID output)
4~20mA DC, load impedance ≤ 600
Ω
(continuous PID output)
Super 2 degree-of-freedom PID (SG-PID algorithm),
Auto-Tuning
ON : ≤ 1K
Ω
, OFF : ≥ 100K
Ω
(external control SV1,2)
TC: K, J, T, E, R, B, S, L, N, U, C(W5), D(W3)
Platinum RTD: KPt100(KS), JPt100(JIS), Pt100(DIN)
Current input(A): 4~20mA DC
Voltage input(V): 1~5V DC, -10~20mV DC, 0~100mV DC
Rating 100~240V AC 50~60Hz (voltage operating range: 85~265V AC)
※
Option: Rating 24V AC or DC (voltage operating range: 20~28V DC)
Current input (250
Ω
), Voltage input (TC included)
≥
1M
Ω
(RTD line resistance : ≤ 10
Ω
, when 3-line resistance are the same)
1c 250V AC, 3A(resistance load) electric lifespan ≥ 100,000
(time proportional PID output or ON/OFF output)
4~20mA DC, load impedance ≤ 600
Ω
resolution 1/4,600
PV(process value), SV(set value), MV(manipulated variable[%]),
SPS(sensor module power supply)
1a 250V AC 3A (resistance load)
20 type of independent event output & Control loop break alarm
T32, T33, T37 : 230g T34 : 140g T39 : 320g
+ 30g, if options are added
14
-10~50 / relative humidity 25~85% RH
(but with neither condensation nor freezing)
℃
※