Tempatron PID500 - Alarm Output; Retransmission Output; Main Control Parameters; Zone PID Control

Tempatron PID500
12 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
3.FUNCTION
Control:PIDorON/OFF.
Output:TimeproportioningorLinearDC.
Proportionalband:0to400
Integraltime:0to3600sec
Derivativetime:0to200sec
Cycletime:0.1to100.0sec.
Autotune.
Programmable%output.
O
4programmablecontrolzones.
Control:PIDorON/OFF
Output:Timeproportioning.
Proportionalgain:0to400
Cycletime:0.1to100.0sec.
Heat/Cooldeadbandoverlap:Programmable
.
Range:0/4-20mA.
Action:Retransmission
Updaterate:100ms
Maximumoutputloadresistance:500E
Range:0-5/10V.
Action:Retransmission
Updaterate:100msec
Minimumoutputloadresistance:10K
Maincontrol
ZonePID
Heat-coolPIDmode
Currentoutput
Voltageoutput
3.3.Retransmissionoutput(optional)
4
Specifications
Modes:Deviationhigh,Deviationlow,Band,
Fullscalehigh,Fullscalelow,Sensorbreak.
Operation:AbsoluteorDeviationmode
Hysteresis:Programmable
Hold/Standbymode:Programmable
Annunciator:Programmable
Resetaction:Programmable-Automaticorlatched
Probebreakaction:Upscale
Alarms
4.OPTIONAL
4.1.Remotesetpointinput
0...20mA /0...10V.
100ohms.
-5%...105%.
-1999...9999withfixed1 CforTC/RTDand
asperresolutionselectedforAnaloginput.
O
Inputtype
InputResistance
Overrange
Scalerange
Rating:5A @250VACor30VDC.
Lifeexpectancy:100000cyclesatmaximumloadrating.
Relaycontactoutput
(Relay2,Relay3(optional)
3.2.AlarmOutput
39
FunctionPrompt
Valueor
Selection
Factory
Setting
Levels
ConfigurationRecordSheet
Output
Parametrs
Zone
Settings
38
FunctionPrompt
Valueor
Selection
Factory
Setting
Input
Parametrs
Output
Parametrs
Enter the value or selection for each prompt on this sheet so you will have a
record of how your controller was configured.
Asperinputtype
selected.
Levels
Asperinputtype
selected.
ConfigurationRecordSheet
5
Specifications
Singlephase,fullwavemonitoringofloadcurrents
controlledbymainoutput.
100mA ACoutputfromcurrenttransformer.
0....999.9A.
47ohms.
+ +0.5%offullscale 1digit.
50...400Hz.
LA /HA /BAND.
105%Capacity.
150mA (continuous).
Type
Input
Displayscalerange
Inputresistance
Accuracy
Frequency
Alarmmode
Overrange
Overload
4.2.Heatercurrentmonitorinput
RS485.
0....50 C.
o
85....270VAC/DC.(Optional24VAC/DC)
50/60Hz.
5VA max.
-20....75 C.
o
85%max.RH(noncondensing)from0to50 C.
o
1....99,maximumof32unitsperline.
Halfduplex.
MODBUSRTU.
500mmaximum.
9600,4800,2400,1200,600,300bits/sec.
None,Odd,Even,Mark,Space.
1or2.
100ms(maxandindependentofbaudrate).
Interfacestandard
Operatingrange
Powersupply
Frequency
Powerconsumption
Storagerange
Storagehumidity
Communicationaddress
Transmissionmode
Transmissionprotocol
Transmissiondistance
Transmissionspeed
Parity
Stopbits
Responsetime
4.3.Serialcommunication
5.ENVIRONMENTAL CONDITIONS
6.POWERSUPPLY
2000volts.
2000VAC.
AClinew.r.t.allinputsandoutputs
Allotherinputsandoutputsw.r.t.Relaycontacts
7.ISOLATIONBREAKDOWNRATINGS.