EasyManua.ls Logo

Tempstar F9MAE - Locating the Vent Termination; General

Tempstar F9MAE
54 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
INSTALLATION INSTRUCTIONS Gas Furnace: (F/G)9MAE
36 440 01 4300 02
Specifications subject to change without notice.
Table 13 Approved Combustion-Air and Vent Pipe, Fitting and Cement Materials (U.S.A. Installation)
ASTM
SPECIFICATION
(MARKED ON
MATERIAL)
MATERIAL PIPE FITTINGS
SOLVENT CEMENT AND
PRIMERS
DESCRIPTION
D1527
ABS Pipe Schedule40
D1785
PVC Pipe Schedule40
D2235
For ABS Solvent Cement For ABS
D2241
PVC Pipe SDR21 & SDR26
D2466
PVC Fittings Schedule40
D2468
ABS Fittings Schedule40
D2564
For PVC Solvent Cement For PVC
D2661
ABS Pipe Fittings DWV at Schedule40 IPS sizes
D2665
PVC Pipe Fittings DWV
F438
CPVC Fittings Schedule40
F441
CPVC Pipe Schedule40
F442
CPVC Pipe SDR
F493
For CPVC Solvent Cement For CPVC
F628
ABS Pipe
Cellular Core DWV at Schedule40 IPS
sizes
F656
For PVC Primer For PVC
F891
PVC Pipe Cellular Core Schedule40 & DWV
Figure 40
Vent Coupling and Adapter with
Gaskets
Attach gaskets to vent pipe and combustion air adapters
A13074
Vent Coupling and Adapter
Figure 41 Vent Pipe Flush with Adaptor
VENT PIPE ADAPTER WITH GASKET INSTALLED ON FURNACE.
VENT PIPE IS CUT FLUSH WITH TOP OF ADAPTER. PRIME AND
CEMENT VENT PIPE TO ADAPTER. ALLOW TO DRY BEFORE IN-
STALLING VENT COUPLING.
A13076A
Figure 42 Vent Pipe Flush Showing Coupling
ALIGN NOTCHES IN VENT PIPE COUPLING OVER STAND
OFF ON ADAPTER. TORQUE LOWER CL AMP 15 LBIN. WHEN
REMAINING VENT PIPE IS INSTALLED, TORQUE UPPER
CL AMP TO 15 LBIN.
A13076B
Locating the Vent Termination
General
NOTE: Termination Requirements for the Provinces of
Alberta and Saskatchewan are located at the end of this
section.
Combustionair inlet pipe (Direct Bent/2Pipe system only) and
vent pipe must terminate outside structure, either through
sidewall or roof.
For vent termination clearance, references to National codes
are shown in Figure 58 for Direct Vent/2Pipe system and
Figure 59 for Ventilated Combustion Air system. For exterior
termination arrangements, refer to Figure 58 for Direct
Vent/2Pipe system and Figure 59 for Ventilated Combustion
Air system. Contact Local code authorities for other
requirements to and/or exemptions from the National codes
shown in the figures.
Roof termination is often preferred since it is less susceptible to
damage or contamination, is usually located away from
adjacent structures, is less prone to icing conditions, and often
has less visible vent vapors. Sidewall terminations may require
sealing or shielding of building surfaces with a corrosive

Related product manuals