INSTALLATION INSTRUCTIONS Gas Furnace: (F/G)9MAE
8 440 01 4300 02
Specifications subject to change without notice.
Figure 3 Multipoise Orientations
THE BLOWER IS LOCATED
TO THE RIGHT OF THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED TO THE LEFT.
THE BLOWER IS
LOCATED BELOW THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED UPWARD.
THE BLOWER IS
LOCATED ABOVE THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED DOWNWARD.
THE BLOWER IS
LOCATED TO THE LEFT
OF THE BURNER SECTION,
AND CONDITIONED AIR IS
DISCHARGED TO THE RIGHT.
L12F010
! WARNING
FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in personal injury, death and/or
property damage.
When the furnace is installed in a residential garage, the burners and igni-
tion sources must be located at least 18in. (457 mm) above the floor.
The furnace must be located or protected to avoid damage by vehicles.
When the furnace is installed in a public garage, airplane hangar, or other
building having a hazardous atmosphere, the furnace must be installed
in accordance with the NFPA 54/ANSI Z223.12012 or CAN/CSA
B149.12010. (See Figure 4)
Figure 4 Installation in a Garage
A93044
! WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury, death and/or
property damage.
Do not install the furnace on its back or hang furnace with control com-
partment facing downward. Safety control operation will be adversely af-
fected. Never connect returnair ducts to the back of the furnace. (See
Figure 5)
Figure 5 Prohibited Installations
BACK POSITIONED
DOWNWARD
AIR
RETURN
CUT IN
BACK
BACK POSITIONED
UPWARD
L12F011
Location Relative to Cooling
Equipment
The cooling coil must be installed parallel with, or on the
downstream side of the unit to avoid condensation in the heat
exchangers. When installed parallel with the furnace, dampers
or other flow control must prevent chilled air from entering the
furnace. If the dampers are manually operated, they must be
equipped with means to prevent operation of either unit unless
the damper is in the fullheat or fullcool position.