EasyManua.ls Logo

TESTO 327 - Efficiency and air ratio calculations

TESTO 327
32 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix28
Efficiency referred to Gross Efficiency:
Effg = 100 -
(
()+
()
+
()
)
Efficiency referred to Nett Efficiency:
Effn= 100 -
(
()+
()
+ ()
)
Kgr/Knet/Qgr/Qnet/K1/MH2O/H:
Fuel-specific factors
FT: Flue gas temperature
AT: Ambient temperature
CO: Measured carbon monoxide
value in %
CO
2
: Calculated carbon dioxide
value in %
E
xcess Air (ExAir): =
( -1 )x 100 21%: Oxygen level of air
O
2
: Measured oxygen level in %
A
ir ratio: λ = C0
2
max: Fuel-specific carbon
dioxide value
CO
2
: Calculated carbon dioxide
value
C
arbon monoxide
u
ndiluted: uCO = CO x λ
CO
: Measured carbon
monoxide value
λ: Calculated air ratio
F
lue gas dew point
temperature: FTP = FH20: Flue gas specific water
vapour level in Vol.%
PAbs: Absolute pressure in
mbar/hPa
K
gr
x (FT - AT)
CO
2
(MH
2
O + 9 x H) x (2488 + 2.1 x FT - 4.2 x AT)
Q
gr
x 1000
K1 x CO
CO
2
+ CO
K
net
x (FT - AT)
CO
2
(MH
2
O + 9 x H) x (210 + 2.1 x FT - 4.2 x AT)
Q
net
x 1000
K1 x Q
gr
x CO
Q
net
x (CO
2
+ CO)
ln (
ln (
FH20 x PAbs
610.78
FH20 x PAbs
610.78
)x 234.175
)- 17.08085
CO
2
max
CO
2
21%
21% - O
2