INS877-4 24/26
installation.
If the LED turns green the selected sensitivity setting is too low for the
installation.
Select the next sensitivity level and repeat the test. Continue until a level is
selected whereby the device LED turns red on impact.
Recommended Sensitivity Setting* Material Radius
1 Wood 1m
2 Framed Glass Window 1m
4 Concrete 0.5m
*Based on the testing requirements of EN50131-2-8 : 2016
7.0 Specifications
Note: To be used with PSU’s that have a current limit of 5A or below.
Note: Product is designed for indoor use only.
Specifications
Alarm System
Impaq S & SC
EN50131-2-8:2017, EN50131-2-6:2008
(Impaq SC only)
EN50131-1:2006+A2:2017,
PD6662:2017, Grade 2
Class II
Alarm System Impaq S
Grade 3
EN50131-2-8:2017
EN50131-1:2006+A2:2017,
PD6662:2017, Grade 3
Class II
Operating Voltage 9-16V DC