EasyManua.ls Logo

TFT ADP2000G - Technical Specifications; Technical Data

TFT ADP2000G
48 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Pagina 33 di 48
STDITR01ADP2090EV TECNOFRIGO TUSCANY srl
Technical specifications
Technical data
TECHNICAL DATA
MODEL
ADP
2000
3500
5000
6500
8000
9500
Performances
Dehumidification Capacity *
Kg/h
15,7
28,4
40,3
53,2
61,5
72,4
Fans
Process air flow
m
3
/h
2000
3500
5000
6500
8000
9500
Static pressure
Pa
400
400
400
400
400
400
Fan nominal power
KW
1,1
1,5
2,2
4
5,5
7,5
Reactivation air flow
m
3
/h
700
1200
1700
2200
2600
3100
Static pressure
Pa
400
400
400
400
400
400
Fan nominal power
KW
0,75
0,75
1,1
1,5
1,5
2,2
Drive Motor
Nominal power
W
10
10
10
10
10
10
Regeneration
Regeneration type
Gas
Gas
Gas
Gas
Gas
Gas
Installed power
KW
30
40
60
75
90
110
Natural gas (G20/G25)
mBar
18÷49
18÷49
18÷49
18÷49
18÷49
18÷49
Gas consumption (****)
m
3
/h
2,95
3,94
5,91
7,38
8,86
10,83
Temperature rise in the heating coil
°C
100
100
100
100
100
100
Electrical characteristics
Power supply
Volt/Ph/Hz
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
400/3/50
Maximum power absorbed standard units
KW
2,1
2,5
3,6
5,8
7,3
10,0
Maximum current absorbed standard units
A
5,6
6,6
8,5
13,0
16,0
21,7
Noise level
Sound pressure **
dB (A)
60
64
65
66
69
70
Sound power **
dB (A)
88
92
93
94
97
98
(*) With inlet air at 20°C 60%
(**)Sound pressure level calculated in free field, 10 meters from the unit, directional factor Q = 2 according to ISO 9614.
(***) Electrical protection standard, resistant to water and dust.
(****) 1 Nm
3
/h natural gas = 10,16KW

Table of Contents