STDITR01ADP2090EV TECNOFRIGO TUSCANY srl
Alarm Menu.
Scroll through the pages with the arrow keys to display the various pages. Press the key to set
the correct system date and time. Press the key to reset active alarms. To return to the main menu,
press the key .
ALARMS TABLE
ITEM
Description
Action
Reset
Process Fan Fault
Thermal process fan alarm
Deactivating the unit
Manual
Reactivation Fan Fault
Thermal rigeneration fan alarm
Deactivating the unit
Manual
Motordrive Fault
Thermal alarm motor drive
Deactivating the unit
Manual
Heaters React. Fault
Thermal alarm regeneration heaters or burner alarm
Deactivating
regeneration
Manual
Safety High Temp. React.
High temperature regeneration alarm from limit thermostat and /
or safety
Deactivating
regeneration
Manual
Rotor gear Fault
Rotor Stop alarm
Deactivating
regeneration
Manual
Fault Probe Temp.React.
Regeneration temperature probe error, failed or disconnected
Deactivating
regeneration
Automatic
Fault Probe Temp.Wet
Air
Wei air Temperature probe error, failed or disconnected
Deactivating
regeneration
Automatic
Fault Probe Temp.Pre-
treatment
Pre-treatment temperature probe error, failed or disconnected
Deactivation of pre-
treatment
Automatic
Fault Probe Temp.Post-
treatment
Post-treatment temperature probe error, failed or disconnected
Deactivation of post-
treatment
Automatic
Fault Probe Humidity
Humidity sensor error, failed or disconnected
Deactivating
regeneration
Automatic
Fault Probe Process Air
Flow
Error Probe Speed or Flow Fan Fan Process, failed or disconnected
No action
Automatic
High Temp. Output Wet
Air
High temperature alarm output wet air
Deactivating
regeneration
Automatic
Fault Probe React. Air
Flow
Speed or air flow sensor error regeneration fan, failed or
disconnected
No action
Automatic
Fault Input remote set
Humidity
External set-point signal error humidity, missing or disconnected
No action
Automatic
Fault Input remote set
Temp.
External set-point signal error post-treatment temperature, missing
or disconnected
No action
Automatic
Heaters pre-heating Fault
Thermal alarm pre-heating heaters (if present)
Deactivation of pre-
treatment
Manual
Heaters post-heating
Fault
Thermal alarm post-heating heaters (if present)
Deactivation of post-
treatment
Manual
Humidification Fault
General humidifier alarm (if present)
Deactivating
humidification
Manual
Error configuration ER01
Configuration alarm:
Pre-cooling / heating control has been enabled without having
enabled the pre-treatment temperature probe (parameters CF30,
CF31, CF08).
No action
Automatic
Error configuration ER02
Configuration alarm:
No action
Automatic