Post-cooled / heated control has been enabled without having
enabled the post-treatment temperature probe (parameters CF28,
CF29, CF09).
Configuration alarm:
Moisture control has been enabled without enabling the humidity
probe (parameters CF32, CF05).
Configuration alarm:
The output 4 ... 20mA has been enabled with PWM control for
regeneration, this output must be configured 0 ... 10V (parameters
CF36, CF01).
Configuration alarm:
The calculated Dewpoint or Absolute Humidity was enabled without
having enabled relative humidity and post-treatment probes (CF33,
CF05, CF09).
Configuration alarm:
The air velocity or process air flow rate has been enabled without
enabling the air velocity probe (FA03, FA04, CF13).
Configuration alarm:
The air flow display was enabled in Kg / h without having enabled
the corresponding air, temperature and humidity air probes, and /
or the various channel configuration parameters (FA03, FA04,
CF13).