EasyManuals Logo

Theben KNX Series User Manual

Theben KNX Series
107 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #35 background imageLoading...
Page #35 background image
The application programmes RAMSES 718 P/S
RAMSES 718 P / RAMSES 718 S 35
4.5.2 Measurement values
Designation
Values
Description
TEMPERATURE
Transmit temperature on change of
(internal sensor)
Only valid for
temperature
measurement at the
internal sensor.
not due to a
change
Only send cyclically
(if enabled)
0.2 K
0.3 K
0.5 K
0.7 K
1 K
1.5 K
2 K
Send if the value has changed
by the selected amount since
the last transmission.
Send temperature cyclically
do not send
cyclically
every min,
every 2 min.
every 3 min.
every 45 min.
every 60 min.
How often should it be resent?
Temperature calibration
-64..+64
(x 0.1 K)
Correction value for
temperature measurement if
sent temperature deviates
from the actual ambient
temperature.
Example: Temperature = 20°C
sent temperature = 21°C
Correction value = 10
(d.h. 10 x 0.1°C)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Theben KNX Series and is the answer not in the manual?

Theben KNX Series Specifications

General IconGeneral
Communication ProtocolKNX
Ambient Temperature-5°C to +45°C
Storage Temperature-25°C to +70°C
Protection ClassIP20
Relative Humidity5% to 95%, non-condensing
Operating Voltage24 V DC (via KNX bus)