Typical applications
RAMSES 718 P / RAMSES 718 S 73
5 Typical applications
These typical applications are designed to aid planning and are not to be considered an
exhaustive list.
It can be extended and updated as required.
5.1 Location school: Heating with presence detector and frost
protection via window contact.
The room temperature controller (RTC) controls one or more actuators.
Once someone enters the room the controller has to change to comfort mode, otherwise it
operates in standby mode during the day and in night mode at night.
If a window is opened, the controller has to automatically change to frost protection mode.
A presence detector is used for presence recognition.
The presence telegram is only sent after a switch-on delay so that the heating is not activated if
the room is only occupied for a short time.
In order that no prohibited settings are made, the device RAMSES 718 S (without control
elements) is recommended here.
All windows are fitted with window contacts. These are connected with input E1 on
the device. As an alternative, the external interface of the Cheops drive actuator can also be
used for this.
The window status is sent via a common group address to the window position input object.
The device will recognise when a window is opened and automatically switch to frost protection
mode.
When the window is closed, the previously set operating mode will be restored.
5.1.1 Devices
RAMSES 718 P/S (Order no.7189210/7189200)
PlanoSpot 360 KNX (Order No. 2039100)
TR 648 top2 RC KNX (Order No. 6489212)
Cheops drive (Order No. 7319200)

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Theben KNX Series and is the answer not in the manual?

Theben KNX Series Specifications

General IconGeneral
Communication ProtocolKNX
Ambient Temperature-5°C to +45°C
Storage Temperature-25°C to +70°C
Protection ClassIP20
Relative Humidity5% to 95%, non-condensing
Operating Voltage24 V DC (via KNX bus)