6.4 set point correction
The set point correction enables a dynamic adjustment of the set point to the outdoor
temperature when cooling.
This function prevents too great a temperature deviation between the outside area and the
cooled interior with high outside temperatures.
If the outdoor temperature exceeds a set threshold, adjustment is activated and a corresponding
increase of the set point is calculated.
The current outside temperature for calculating the correction is received via object Outside
temperature.
The set point correction is activated on the RTC Settings parameter page via the
Use set point correction with high outside temperatures parameter and is set on the set point
adjustment parameter page.
The set point correction is internally linked to the RTC, so no bus connection is required.