65
General Troubleshooting
Compressor will not
start
Check supply voltage, amperage of each leg,
contactor and wiring, and overload set point
Contact Customer Service for assistance
Check supply voltage, amperage of each leg,
contactor and wiring, and overload set point
Contact refrigeration service technician
Contact refrigeration service technician
Low refrigeration pressure sensor
Check for proper range, replace if faulty
High refrigerant
pressure
Dirty air filters (air-cooled units only)
Air flow obstruction (air-cooled units only)
Make sure chiller is installed in accordance
with recommendations in this manual
High ambient air temperature (air-cooled units only)
Ambient temperature must be reduced below
110°F
Condenser fan motor (air-cooled units only)
Condenser fan cycling control (air-cooled units only)
Confirm proper operation, replace if faulty
Plugged condenser (water-cooled units only)
Insufficient condenser water flow (water-cooled units
only)
Make sure chiller is installed in accordance
with the recommendations of this manual
High condenser water temperature (water-cooled
units only)
Condenser water temperature must be
reduced below 100°F
Condenser water regulating valve
Check setting, replace if faulty
Refrigerant circuit overcharged
Contact refrigeration service technician
High refrigerant pressure sensor
Low flow through evaporator
Adjust flow to proper level
Freezestat control module
Check for proper setting (Protected Setting)
Low pump discharge
pressure
Switch 2 legs of the incoming power
High pump discharge
pressure
Closed valves in process piping
Obstruction in piping or process