EasyManuals Logo

Thermia iTec XT Installation Guide

Thermia iTec XT
60 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image
4.3.2 Installation location requirements
The outdoor unit shall be installed in an open space that is always ventilated.
The national f-gas regulations shall be observed.
For installation inside a building (this applies either to indoor or outdoor units installed inside) a minimum room floor area of space
conditioned is mandatory according to IEC 60335-2-40:2018.
To handle, purge, and dispose the refrigerant, or break into the refrigerant circuit, the worker should have a certificate from an
industry-accredited authority.
4.3.3 Preparation of fire extinguisher
If any hot work is to be done, an appropriate fire extinguishing equipment should have been available.
A dry powder or CO2 fire extinguisher shall be equipped at the charging area.
4.3.4
Ignition sources free
Caution Make sure to store the units in a place without continuously operating
ignition sources (for example, open flames, an operating gas appliance
or an operating electric heater).
The installer shall not use any ignition sources with the risk of fire or explosion.
Potential ignition sources shall be kept away from the work area where the flammable refrigerant can possibly be released to the
surrounding.
The work area should be checked to ensure that there are no flammable hazards or ignition risks. The “No Smoking” sign shall be
attached.
Under no circumstances shall potential sources of ignition be used while in detection of leakage.
Safe parts are the ones with which the worker can work in a flammable atmosphere. Other parts may result in ignition due to leak-
age.
Replace components only with parts specified by Thermia. Other parts may result in the ignition of refrigerant in the atmosphere
from a leak.
4.3.5
Area ventilation
Make sure that the work area is well ventilated before performing any possible hot work.
Ventilation shall be adequate during the installation work.
The ventilation should safely disperse any released gases and expel them into the atmosphere, away from the work area.
4.3.6
Leakage detection methods, if checking for possible leakage
The leakage detector shall be calibrated in a refrigerant-free area.
Make sure that the detector is not a potential source of ignition.
The leakage detector shall be set to the LFL (lower flammability limit).
The use of detergents containing chlorine shall be avoided for cleaning because the chlorine may react with the refrigerant and
corrode the pipes.
If leakage is suspected, naked flames shall be removed.
If a leakage is found while in brazing, the entire refrigerant shall be recovered from the product or isolated (e.g. using shut-off
valves). It shall not be directly released to the environment. Oxygen free nitrogen (OFN) shall be used for purging the system before
and during the brazing process.
The work area shall be checked with an appropriate refrigerant detector before and during work.
Ensure that the leakage detector is appropriate for use with flammable refrigerants.
Installation Guide
iTec XT
Thermia AB AWIXT01IG0102
27

Other manuals for Thermia iTec XT

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Thermia iTec XT and is the answer not in the manual?

Thermia iTec XT Specifications

General IconGeneral
BrandThermia
ModeliTec XT
CategoryMeasuring Instruments
LanguageEnglish