TS 870 Transfer Switch
PM062 REV 11 16/04/19 5 Thomson Power Systems
Related Product Instruction Manuals
• TS 870 Quick Start Instruction Manual, PM150
• TSC 900 Transfer Switch Controller, PM151
• TSC 900 Modbus
TM
Communication, PM152
Contact Thomson Power Systems, to obtain these instruction manuals. Soft copy of the most
current versions of these manuals are available at www.thomsonps.com
.
2. EQUIPMENT STORAGE
The following procedures are required for correct storage of the transfer switch prior to installation.
CAUTION
Failure to store and operate equipment under the specified environmental conditions
may cause equipment damage and void warranty.
2.1. EQUIPMENT STORAGE
The transfer switch shall be stored in an environment with a temperature range not
exceeding -4° to +158° Fahrenheit (-20° to +70° Celsius) and a humidity range not
exceeding 5%-95% non-condensing. Before storing, unpack sufficiently to check for
concealed damage. If concealed damage is found, notify the ATS supplier and the
Carrier immediately. Repack with the original, or equivalent packing materials. Protect
from physical damage. Do not stack. Store indoors in a clean, dry, well ventilated area
free of corrosive agents including fumes, salt and concrete/cement dust. Apply heat as
necessary to prevent condensation.
3. NOTES TO INSTALLER
DANGER
Arc Flash and Shock Hazard. Will cause severe injury or death.
Do not open equipment until ALL power sources are disconnected
This equipment must be installed and serviced only by qualified electrical
personnel utilizing safe work practices and appropriate Personal Protective
Equipment (PPE). Failure to do so may cause personal injury or death