TS 880
AUTOMATIC TRANSFER SWITCHES
INSTALLATION, OPERATING &
SERVICE MANUAL
PM064 REV 8 10/01/25

Table of Contents

Questions and Answers

  • J
    James MartinezJul 31, 2025
    What to do if my THOMSON Switch won't re-transfer to the utility source?
    • M
      Michelle EvansJul 31, 2025
      If your THOMSON Switch does not re-transfer to the utility source after power is restored, there might be several reasons. First, check if the isolation plug is out or the utility disconnect switch is de-energized; if so, switch to the energized position. Also, verify that a test mode hasn't been activated by checking the TSC 800 controller. Ensure the utility voltage is within pre-programmed limits, and check the utility source for adequate voltage.
  • M
    Mark SilvaAug 8, 2025
    What to do if my THOMSON Switch won't transfer to the generator after a utility power failure?
    • T
      Travis JonesAug 8, 2025
      If your THOMSON Switch fails to transfer to the generator source when the utility source fails, several factors could be at play. It could be that the generator set isn't producing enough voltage or frequency, or the output circuit breaker is open. Another possibility is that the TSC 800 has an incorrect voltage programmed for the system voltage. Also, the warmup time delay function might not have timed out yet; verify the TSC 800 timer setting. Finally, a 'Transfer Fail' alarm might be activated on the TSC 800; determine the cause of the alarm and rectify it before resetting the TSC 800. You can verify output signals with circuit board mounted diagnostic LEDs.
  • J
    James StewartAug 14, 2025
    What to do if there's no power at the load terminals of my THOMSON TS 880?
    • S
      simonericAug 15, 2025
      If power isn't available at the load terminals of your THOMSON Switch, but the power switching device seems closed to a live source, it's possible that the power switching device's over current protection unit has opened due to a fault on the system. To resolve this, correct the fault and manually reset the power switching device in the transfer switch by moving it off and then on again using the manual operating handle.
  • W
    William MooreAug 21, 2025
    Why is my THOMSON TS 880 transferring to generator power without a utility power failure?
    • L
      Lauren McintyreAug 21, 2025
      If your THOMSON Switch transfers to the generator source even without a power failure in the utility source, it could be due to a few reasons. A test mode might have been activated; check the TSC 800 controller. Alternatively, the utility supply voltage might be slightly below the voltage sensing setpoints; in this case, verify that the TSC 800 has the correct voltage program setting for the system voltage. You can verify output signals with circuit board mounted diagnostic LEDs. It's also possible that the utility power switching device has tripped due to an over current condition; determine the cause of the alarm and rectify it before the TSC 800 is reset.

Summary

TS 880 ATS Manual: Installation, Operation, Service

Installer Notes and Warnings

Upstream Circuit Protection & Electrical Connections

Guidance on protective devices and electrical connection tightness.

Integral Over Current Protection Configuration

Configuration details for switches with built-in over current protection.

ATS General Description

Product Model Code Explained

Explains the 21-digit product code structure and its definitions.

Commissioning Procedures Overview

Step-by-step guide for initial setup and testing of the ATS.

ATS Theory of Operation

Over Current Protection (OCP)

Integral OCP Configuration Options

Details on models with built-in over current protection.

Servicing Transfer Switch Mechanisms

Upstream Circuit Protective Device Requirements

Ground Fault Site Test Requirements

Troubleshooting ATS Issues

100 A-1200 A Molded Case ATS Troubleshooting

Common symptoms and causes for 100A-1200A molded case ATS.

800 A-4000 A Insulated Case ATS Troubleshooting

Common symptoms and causes for 800A-4000A insulated case ATS.

Power Switching Device Troubleshooting

Replacement Parts List

Appendix A: Commissioning Procedures

Pre-Commissioning Checks

Checks to be performed before the commissioning agent arrives.

Final Commissioning Steps

Steps for on-site final commissioning and verification.

ATS Load Test Procedure

Steps for performing load tests on the ATS.

Appendix B: Seismic Certificate

THOMSON TS 880 Specifications

General IconGeneral
BrandTHOMSON
ModelTS 880
CategorySwitch
LanguageEnglish