EasyManua.ls Logo

Thytronic NA011 - Automatic Reclosure - 79

Thytronic NA011
95 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FUNCTION CHARACTERISTICS
41
NA011 - Manual - 05 - 2022
Automatic reclosure - 79
Preface
The automatic reclosure function is well-used on overhead lines (when faults are self-extinguish
after tripping of protection relays).
To activate the Auto-reclose function the CB state acquisition must be enabled!
Operation and settings
[1]
The following sequences may be selected:
Rapid reclosure,
Rapid reclosure + slow reclosure
Rapid reclosure + slow reclosure followed by one or more delayed reclosures (1...5).
Starting of the automatic reclosing function can be raised by internal protective elements or exter-
nally by means binary input signals (eg: external protection device contacts or operating switches).
The following logics may be set (binary input IN3 allocation):
External trip; activation command (pulse),
Enabling; activation command (On = Enable).
The element may be enabled or disabled by setting ON the 79 Enable parameter available inside
the Set \ AutoReclose-79 menu.
The following output functions may be drive the output relays:
CB reclosing command (79 Close); it is needful for the auto reclosure function.
Cycle in progress (79 Run).
Reclosure fail (79 Fail).
The following timers are provided:
t
rdt
Rapid reclosure dead time
t
sdt
Slow reclosure dead time
t
r
Reclaim time
t
d
Slow reclosure fault discrimination time
Note 1 The CB state acquisition must be enabled; if CB check = None the 79 function is disabled
all-F79.ai
79 Enable
52a, 52b, 52a&52b
79 Trigger
79-Close
79-Run
79
79-Fail
Trip I>
&
Trip I>
Trip I>>
&
Trip I>>
Trip IE>
&
Trip IE>
Trip I>>
&
Trip I>>
Trip IE>>
&
Trip IE>>
Trip ProtExt
&
Trip Remote
1
Binary input INx
T 0
Logic
INx
t
ON
INx
t
ON
INx
t
OFF
T0
n.o.
n.c.
INx
t
OFF
Binary input INx
T 0
Logic
INx
t
ON
INx
t
ON
INx
t
OFF
T0
n.o.
n.c.
INx
t
OFF
Binary input INx
T 0
Logic
INx
t
ON
INx
t
ON
INx
t
OFF
T0
n.o.
n.c.
INx
t
OFF
Binary input INx
T 0
Logic
INx
t
ON
INx
t
ON
INx
t
OFF
T0
n.o.
n.c.
INx
t
OFF
79 Remote
Block2 IPh/IE
ModeBLIN1
T 0
t
B-Iph
50-51S2_BL-diagram.ai
1
1
1
1
1
t
B-Iph
t
B-IE
BLK1I>>
&
&
BLK2IN I>>
&
&
Enable (ON Enable)
I>>BLK1
Block2 input enable (ON Enable)
Pilot wire input
Pilot wire output
&
I>>BLK2IN
Block1
BLK2IN-Iph
Start I>>
Trip I>>
Iph Block2
IE Block2
IE/Iph Block2
BLK2IN-IE
tB timeout
Block2 input
Block1
FROM EARTH FAULT PROTECTIONS
FROM ANY PROTECTIONS
OFF
ON IPh
ON IPh/IE
ON IE
BLIN1
Block1
T 0
t
B-IE
Block2 IE
Block1, Block2
TRIPPING MATRIX
(LED+RELAYS)
TRIPPING MATRIX
(LED+RELAYS)
1
1
ModeBLOUT1
A
B
C
D
BLOUT1
Block2 output
1
1
t
F-IPh
t
F-IPh/IE
t
F-IE
ST-Iph BLK2
ST-IE BLK2
&
Block2 output
(ON Enable)
I>>BLK2OUT
Start I>>
1
T 0
t
F-IPh/IE
T 0
t
F-IPh
T 0
t
F-IE
I>> Blk2 OUT
I> Blk2 OUT
I>>> Blk2 OUT
I
E
>> Blk2 OUT
I
E
> Blk2 OUT
I
E
>>> Blk2 OUT
BLK2OUT-Iph
BLK2OUT-Iph/IE
BLK2OUT-IE
A = OFF
B = ON IPh
C = ON IPh/IE
D = ON IE
BLK2OUT-IPh-K
BLK2OUT-IPh-L
BLK2OUT-IPh/IE-K
BLK2OUT-IPh/IE-L
BLK2OUT-IE-K
BLK2OUT-IE-L
tB-K
tB-L
Phase overcurrent (50/51) - Logic diagram of the blocking signals concerning the second element (I>>)
CB check
IN3 select
79 Enable 79 Mode 79 MC-td-EN 79 MO-RES
N.DAR
t
rdt
t
sdt
t
r
t
d
General logic diagram of the automatic reclose function - 79

Table of Contents

Related product manuals