EasyManua.ls Logo

Thytronic NA011 - Residual Overcurrent - 50 N;51 N

Thytronic NA011
95 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
FUNCTION CHARACTERISTICS
36
NA011 - Manual - 05 - 2022
Residual overcurrent - 50N/51N
Preface
The residual current is:
Measured for NA011#xxx2 and NA011#xxx3 versions from one residual current input with second-
ary nominal current selectable at 1 A or 5 A through DIP-switches or,
Calculated for NA011#xxx0 and NA011#xxx1 versions by the vector sum of the three phase currents,
measured by three 1A or 5A CTs or by three LPCT type sensors.
Two operation thresholds, independently adjustable (I
E
>, I
E
>> with adjustable delay (t
E
>,
t
E
>>) are available; they may be programmed with definite or inverse time according the IEC, ANSI/
IEEE or I2T standard curves.
Operation and settings
The residual fundamental frequency current) is compared with the setting value. Current above the
associated pickup value is detected and a start is issued. After expiry of the associated operate
time a trip command is issued; if instead the current drops below the threshold, the element it is
restored.
The thresholds (I
E
> and I
E
>>) may be programmed with definite or inverse time according the follow-
ing characteristic curves:
Standard Inverse Time (IEC 255-3/BS142 type A or SIT): t = 0.14 · t
E
>
inv
/ [(I
E
/I
E
>
inv
)
0.02
- 1]
Very Inverse Time (IEC 255-3/BS142 type B or VIT): t = 13.5 · t
E
>
inv
/ [(I
E
/I
E
>
inv
) - 1]
Extremely Inverse Time (IEC 255-3/BS142 type C or EIT): t = 80 · t
E
>
inv
/ [(I
E
/I
E
>
inv
)
2
- 1]
Moderately Inverse (ANSI/IEEE type MI): t = t
E
>
inv
· {0.01 / [(I
E
/I
E
>
inv
)
0.02
- 1] + 0.023}
Very Inverse (ANSI/IEEE type VI): t = t
E
>
inv
· {3.922 / [(I
E
/I
E
>
inv
)
2
- 1] + 0.098}
Extremely Inverse (ANSI/IEEE type EI): t = t
E
>
inv
· {5.64 / [(I
E
/I
E
>
inv
)
2
- 1] + 0.024}
I-squared-t (I
2
t = K): t = 16 · t
E
>
inv
/ (I
E
/I
E
>
inv
)
2
where:
t: operate time
I
E
>: pickup value
t
E
>
inv
: operate time setting
For all inverse time characteristics, following data applies:
Asymptotic reference value (minimum pickup value): 1.1 I
E
>
Minimum operate time: 0.1 s
Range where the equation is valid:
[1]
1.1 ≤ I
E
/I
E
>
inv
≤ 20
If I
E
>
inv
pickup 2.5 I
En
, the upper limit is 10 I
En
For all definite time elements the upper limit for measuring is 10 I
En
for version with CTs inputs and
35 I
n
for version with LPCTs inputs.
All elements can be enabled or disabled by setting the relative start and/or trip output to a selectable
relay inside the Set \ Relays menu.
For each threshold a reset time can be set (t
E>RES
, t
E>>RES
) useful to reduce the clearing time for
intermittent faults.
Note 1 When the input value is more than 20 times the set point , the operate time is limited to the value corresponding to 20 times the set point
General operation time characteristic for the residual overcurrent elements - 50N/51N
I
E
I
E
>>
t
E
>
t
E
>>
I
E
>
t
TRIP
Timers-F50N-51N.ai
IE> element residual overcurrent (50N/51N) - Timers
IE> Start
IE> Trip
t
E>
t
E>
RESET
INPUT
t
E>RES
t
E>RES
t
E>RES
t

Table of Contents

Related product manuals