350
FUNCTION CHARACTERISTICS
Virtual I/O
Preface
Through ThyVisor tool the type of operation and links between thirty-two outputs (Virtual Output -
VOUT1 ... 32) and thirty-two virtual inputs (Virtual Inputs - VIN1 ... VIN32) may be defined using RPC
or IEC 61850 communication protocols over Ethernet network.
Special features are:
Availability of thirty-two inputs and thirty-two outputs independently programmable by the user
Simplify wiring using one channel as the Ethernet
Eliminate the need to install communication devices and / or external conversion
Significantly reduce costs
Dynamically change from sw connections and associated functions
Applications
With XMR-D relay virtual I / O can be usefully employed for:
Transmit information between protections installed in distance
Achieve accelerated logic discrimination in which some protection elements can be blocked by the
activation of the downstream protection start
Circuit Breaker commands, Selection of setting profiles, Remote trip, etc...
Virtual Outputs:
The t
V
, t
F-IPh
and t
F-IE
timers start when the virtual output becomes active; when the counters expire
the virtual outputs are forced OFF; if the t
V
, t
F-IPh
and t
F-IE
timers are cleared the virtual output fol-
lows the state of the input (Start, Trip, PLC, IN).
The setting ranges are:
Start dropout time for voltage protections (t
V
) 0.00...30.00 s (step 0.01 s)
Start dropout time for phase protections (t
F-IPh
) 0.00...30.00 s (step 0.01 s)
Start dropout time for ground protections (t
F-IE
) 0.00...30.00 s (step 0.01 s)
Trip reset (t
Trip)
0.00...30.00 s (step 0.01 s)
All the parameters are available inside the Set \ Virtual Outputs \ Settings menu.
Virtual Inputs:
LinkLoss timer 3.0...60.0 s (step 0.1 s)
When the Virtual input is set for Remote Trip function, in the event of a network crash, when the
counters expire the remote trip is forced.
The parameter is available inside the Set \ Virtual Inputs \ Settings menu.
PROTECTION RELAY
XMR-D
IN32
OUT1
OUT2
OUT...
OUT32
IN...
IN3
IN2
IN1
PROTECTION RELAY
XMR-D
IN32
OUT1
OUT2
OUT...
OUT32
IN...
IN3
IN2
IN1
Customizable connections
XMR-D EQUIPMENT MANUAL
Ed. 2.9 - 02/2021

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Thytronic XMR-D and is the answer not in the manual?

Thytronic XMR-D Specifications

General IconGeneral
BrandThytronic
ModelXMR-D
CategoryProtection Device
LanguageEnglish

Related product manuals