Rack Control Module
TM
Product Manual
Rev. 1.2, May 9, 2014 Page 33
Provide power from a well charged battery or DC power source, 8VDC to 28VDC, steady
output. Confirm this voltage using a Digital Multimeter. Do not use a battery charger for
testing.
The following troubleshooting steps are organized by system or circuit function and
symptoms. These are some of the most common system wiring and component failures
along with suggested troubleshooting and repair steps.
As an alternative, please also refer to the pictorial Rack Control Module Operator Guide
for loading, unloading, alarm and error conditions.