Filter Replacement
Filters should be replaced at least annually, or more regularly dependent on environmental conditions. The aurastat® will
indicate lter change required in line with the Filter Change Interval setting. Replacement Filters are available from Titon
Direct. www.titondirect.co.uk
Titon HRV Q Plus Filters are available in two grades G3 and G4. Filter media should be replaced like for like.
Filter Part numbers in table below. The Unit part number can be found on the serial number label xed to the top and front
of the unit.
G3 Filters - Both faces white. G4 Filters - One face white, one face blue.
Model Part Number
G3 Filter Set
2 framed lters
G4 Filters Set
2 framed lters
HRV1.25 Q Plus
TP406x
TP416x
XP40032/099 XP46022/099
HRV1.35 Q Plus
TP408x
TP418x
HRV1.6 Q Plus
TP409x
TP419x
XP2010671/099 XP2010897/099
HRV1.65 Q Plus
TP410x
TP420x
HRV1.75 Q Plus
TP404x
TP414x
XP40133/099 XP46133/099
HRV2 Q Plus
TP401x
TP411x
HRV2.85 Q Plus
TP407x
TP417x
HRV3 Q Plus
TP402x
TP412x
How to Change Filters
1. Remove Front Cover or Filter Covers.
2. Slide out Filters.
3. HRV 1.6, 1.65, 1.75, 2, 2.85 & 3 Q Plus models use unequal Filters. Make a note of which side of the unit the lter with
the shorter lter media is. The positions of lters is marked on the units.
Shorter Media Filter
4. Replace Filters by carefully sliding in the replacement lters. Ensure that lters are replaced in the same positions as
they were removed. The positions of lters is mark on the units.
5. Replace the Front Cover or Filter Covers.
auralite® Filter Notication Reset
Ensure the HRV is powered up. To clear the auralite® lter notication press & hold the reset switch with a ball point pen
or similar object for 10 seconds. The switch is located behind the small hole in the front of the auralite®. All lights will
momentarily be illuminated indicating a successful reset.