4. INSTALLATION
4.1. Installing the VX-3000DS in the Cabinet Rack
4.2. Battery Installation
If the short occurs, the unit may fail.
Follow the instructions in this section for safe and secure connection.
p. 24
to prevent shorts between positive and negative terminals.
[Cable end treatment]
and treat its end as follows.
Usable cable diameter: AWG 6 – AWG 0 (AWG 1/0)
Stripped length: 30 mm ± 5 mm
Cross sectional area: 16 – 50 mm
2
[Cautions on cable connection to the battery terminal]
terminal, be sure to fully open the cable clamp by turning
the terminal screw counterclockwise.
Battery terminal
Terminal screw
Cable clamp
Fully open. Too narrow to
clamp the cable
Incorrect
Rack mounting screw
5 x 12
WARNING