18
model 3000 PROFIBUS Module Users Manual
Chapter 4 Operation and Function
4
See section 2.5
See section 9.3
See chapter 5
See chapter 6
See section 2.5
Figure 4-4 Startup procedure example
2
Set the PF312.
Turn off MD4, 5, 6, and 7 of MODE2 setup switch.
(When there is an error, hold transmission data and set both transmit and receive)
Set MODE1 setup switch to 6. (32 word transmission)
3
Install each module and connect cables.
Install each module on the base unit.
Connect PF311 and PF312 with transmission cable.
(Turn on both terminating resistors with connector or module.)
Connect the PC and PF311 with connection cable.
4
Set PF311 with the configurator (SyCon).
Insert master (PF311) (select HMS Profibus-DP Master.)
Insert slave (PF312) (select HMS AnyBus-S.)
Set the slave transmission word count.
(Select 32 word transmission (IN/OUT: 64 bytes (32 words).)
Set transmission speed with bus parameter.
Download settings to PF311.
5
Set each station with integrated controller engineering tool.
Set PF311 from the master side station.
Set PF312 from the slave side station.
Create S3 controller program and download it.
6
Run each controller.
When transmission starts, check the status of the PF311 and PF312 LEDs.
Transmission is normal if they are as follows:
PF311...RDY, RUN, TOKEN, ACC on, ERR off
PF312...ONL, ACC on, OFL, DIAG off
7
Check the transmission data with each controller.
Check that expected data is transmitted on the master and slave side.