6F8C0921
19
5
Chapter 5 Transmission
Parameter Setup
When using this module, you must set the transmission parameters using the
PROFIBUS configurator, in addition to the controller setup and registration.
Use the following PROFIBUS configurator:
Name:
PROFIBUS SYSTEM CONFIGURATOR
HMS SYCON
Manufacturer:
HMS INDUSTRIAL NETWORKS AB
Supported OS:
Windows95, Windows98, WindowsNT4.0 with Service Pack3 or higher,
Windows2000
The basic setup procedure is described below. Refer to the manuals for the above
configurator for more information.
Start HMS SyCon.
Select [File]-[New] to create a new file, open the busline window and enter the
configuration mode.
Add masters on the bus. (Select ABM-PDP provided by HMS for PF311.)
Add a slave and assign it to a master. (Select AnyBus-S provided by HMS for PF312.)
Set the I/O modules and parameters for the added slave.
Select a master to check the attributes and connection between devices and then
check other masters to verify the setting.
Select the baud rate and bus parameters.
Set how HMS SyCon and master should communicate.
Save the settings.
Select the port to download to the master and download.
Connect the PROFIBUS cable between devices. Enter debug mode to check the
communication status and perform I/O monitor test.
Print out the documents of the set PROFIBUS system.
When PROFIBUS runs normally, install the applications.