28
model 3000 PROFIBUS Module User’s Manual
Chapter 8 RAS Information
8
(2) Healthy counter
Indicates the normal operating status of the PF module.
Indicates that the PF module is operating normally. A 16-bit counter that is updated
every 100 ms.
Returns to 0 after FFFFh.
(3) Device error
Indicates the transmission module error status.
The error status is indicated with the following codes:
(4) PROFIBUS-DP status
Indicates the transmission module operating status.
Table 8-3 Healthy counter
F E D C B A 9 8 7 6 5 4 3 2 1 0
0001h Healthy Counter
F E D C B A 9 8 7 6 5 4 3 2 1 0
0002h Device Error
Table 8-4 Device error
Error No. Symbol Description
0 - No error
14 OS module, firmware download in progress
50 RAM_TEST RAM check error
53 FLASH_TEST FLASH PROM checksum error
100-107 SYSTEM Internal system error
200 Unknown_IRQ Unknown interrupt detected
201 Watchdog Watchdog timer error
202 TX_IRQ Unknown send interrupt from serial channel detected
203 RX_IRQ Unknown receive interrupt from serial channel
detected
252 Download active Firmware or database download in progress
253 Bootloader active Bootstrap loader activeFirmware stopped
Table 8-5 PROFIBUS-DP status
Address 15 0
0010h Master status Global error bit
0011h Error event Error causing remote address
0012h Bus error counter
0013h Timeout counter
0018h Slave setting status (bit for each slave)
0020h Slave operating status (bit for each slave)
0028h Slave diagnostic (bit for each slave)