30
model 3000 PROFIBUS Module User’s Manual
Chapter 8 RAS Information
8
(d) Error event
(e) Bus error counter
Severe bus error counter
(f) Timeout counter
PROFIBUS telegram exclusion count
One reason for incrementing the counter might be bus cable short.
7 6 5 4 3 2 1 0
Err_Event
Table 8-9 Error events
Value Error Event Cause Action
0 Remote node operating normally
3 Remote node internal function
invalid
Remote Check the setting and use correct GSD
file
9 No response for data Remote Re-examine bus cable
17 No response from slave Remote Re-examine bus cable andre-examine
remote node address
18 Master not participating in token ring Master Re-examine master node address
50-53 Internal error Master Contact Toshiba
54 No master parameter Master Download setup information again
55 Master parameter error System
design
Contact Toshiba
56 No remote node parameter System
design
Download setup information again
57 No remote node parameter System
design
Contact Toshiba
58 Duplicate remote node address System
design
Re-examine remote node address
59 Transmit address out of range System
design
Re-examine transmit address
60 Receive address out of range System
design
Re-examine receive address
61 Duplicate receive area System
design
Re-examine receive address
62 Duplicate transmit area System
design
Re-examine transmit address
202 Insufficient space Master Contact Toshiba
212 Setup data read error Master Download setup information once more
213 System error Master Contact Toshiba
Others Unprescribed error - Contact Toshiba
Table 8-10 Bus error counter
F E D C B A 9 8 7 6 5 4 3 2 1 0
Bus_Error_count
Table 8-11 Timeout counter
F E D C B A 9 8 7 6 5 4 3 2 1 0
Time_out_count