18 G9 ASD Quick Start Guide
Terminal Descriptions
Note: The programmable terminal assignments may be accessed and changed from their
default settings as mapped on pg. 34 or via the Direct Access method: Program
Direct Access Applicable Parameter Number. See the section titled Program
Mode Menu Navigation on pg. 34 for the applicable Direct Access parameter
numbers.
For further information on terminal assignments and default setting changes, see the
sections titled Terminal on pg. 35 and Default Setting Changes on pg. 62.
Note: See the section titled Cable/Terminal/Torque Specifications on pg. 75 for the G9 ASD
conductor and terminal electrical specifications.
Note: Programmable terminals will not retain their settings indefinitely in the event of a
power loss. Connect an external +24 VDC supply to the SU+ terminal to retain the
programmable settings in the event of Control Power loss (see Figure 20 on pg. 22).
ST — The default setting for this terminal is the Standby mode controller. As the default setting, this
terminal must be activated for normal system operation. The ST terminal is activated by connecting CC
to this terminal (Sink mode). When deactivated, OFF is flashed on the LED screen and the Not-Ready-
to-Run indicator is displayed on the LCD Screen (see Figure 22. on pg. 27). This input terminal may be
programmed to any of the functions that are listed in the G9 ASD Installation and Operation Manual.
RES — The default setting for this terminal is Reset. The RES terminal is activated by connecting CC
to this terminal (Sink mode). A momentary connection to CC resets the ASD and any fault indications
from the display. Reset is effective when faulted only. This input terminal may be programmed to any
of the functions listed in the G9 ASD Installation and Operation Manual (see F114).
F — The default setting for this terminal is Forward run command. The F terminal is activated by
connecting CC to this terminal (Sink mode). This input terminal may be programmed to any of the
functions listed in the G9 ASD Installation and Operation Manual (see F111).
R — The default setting for this terminal is Reverse run command. The R terminal is activated by
conn
ecting CC to this t
erminal (Sink mode). This input terminal may be programmed to any of the
functions listed in the G9 ASD Installation and Operation Manual (see F112).
S1 — The default setting for this terminal is Preset Speed 1. The S1 terminal is activated by
connecting CC to this terminal (Sink mode). This input terminal may be programmed to any of the
functions listed in the G9 ASD Installation and Operation Manual (see F115).
S2 — The default setting for this terminal is Preset Speed 2. The S2 terminal is activated by
connecting CC to this terminal (Sink mode). This input terminal may be programmed to any of the
functions listed in the G9 ASD Installation and Operation Manual (see F116).
S3 — The default setting for this terminal is Preset Speed 3. The S3 terminal is activated by
connecting CC to this terminal (Sink mode). This input terminal may be programmed to any of the
functions listed in the G9 ASD Installation and Operation Manual (see F117).
S4 — The default setting for this terminal is Preset Speed 4. The S4 terminal is activated by
connecting CC to this terminal (Sink mode). This input terminal may be programmed to any of the
functions listed in the G9 ASD Installation and Operation Manual (see F118).
RR — The default function assigned to this terminal is Frequency Mode 1. The RR terminal accepts a
0 – 10 VDC input signal that is used to control the function assigned to this terminal. This input terminal
may be programmed to control the speed or torque of the motor via an amplitude setting or to regulate
by setting a limit. The gain and bias of this terminal may be adjusted for application-specific suitability
(see F210 – F215). See Figure 20 on pg. 22 for an electrical depiction of the RR terminal.
Standby
Reset
Forward
Reverse
Preset Speed 1
Preset Speed 2
Preset Speed 3
Preset Speed 4
RR
Frequency
Mode 1