32 G9 ASD Quick Start Guide
Feedback (inst) — Provides a status of the Real Time Feedback in Hz.
Feedback (1 second) — Provides a status of the 1-Second Averaging feedback in Hz.
Torque Displays the Output Torque as a percentage of the rated capacity of the ASD.
Torque Reference Displays the Torque Reference as a percentage of the maximum torque
available.
Torque Current Displays the torque-producing current value.
Excitation Current Displays the current value required to produce the excitation field.
PID Feedback
— Provides a status of the PID Real Time Feedback in Hz.
Input Power
— Displays the Input Power in Kilowatts (kW).
Output Power
— Displays the Output Power in Kilowatts (kW).
Pattern Group NumberDisplays the active Pattern Run Group Number.
Pattern Group CycleDisplays the cycle number of the active Pattern Run Group.
Pattern Group PresetDisplays the active Preset Speed being run of the active Pattern Run
Group.
Pattern TimeDisplays the remaining time for the active Pattern Run Group.
RR
— Displays the RR input value as a percentage of the full range of the RR value (potentiometer
input).
VI/II (V/I)
— Displays the V/I input setting as a percentage of the full range of the V/I value.
Note: The isolated VI/II (V/I) input terminal may receive Current or Voltage to control the
output speed or the output torque. The input signal type must be selected at SW301 on
the Terminal Board.
The V input setting of SW301 is used for the 0 – 10 VDC analog input signal and the
I input setting of SW301 is used for the 0 – 20 mA analog input signal. Either may be
used as a frequency or torque command source. See parameter F201 for more
information on the setup of this terminal.
The LCD Screen shows the VI/II (V/I) terminal as VI/II (the additional character I is
used to indicate “Input.”).
RX
— Displays the RX input setting as a percentage of the full range of the RX value (-10 to
+10 VDC input).
RX2 Option (AI1)
— Displays the RX2 input setting as a percentage of the full range of the RX2
value.
Note: The RX2 function is available on the Expansion IO Card Option 1 option board
(P/N ETB003Z) only.
Trip CodeDisplays None if there are no errors, or displays one of the associated Fault Codes
listed in the G9 ASD Installation and Operation Manual if there is an active Fault (e.g.,
E = Emergency Off).
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net