ACE-tronics G9 ASD Installation and Operation Manual 47
Command and Frequency Mode Control
Command control includes instructions such as Stop, Run, Jog, etc. The source of the Command 
signal must be established for normal operation.
Frequency commands control the output speed of the ASD. The source of the frequency control signal 
must be established for normal operation.
The source of the command control and frequency control may be either internal or external. Once the 
source signal is selected for either function, the system may be configured to use the selected signal all 
of the time or switch under user-defined conditions.
Command and Frequency control may be carried out using any one of several control methods (signal 
sources) or combinations thereof. In the event that multiple control commands are received, the signal 
sources are assigned priority levels. The primary control method for Command and Frequency control 
uses the settings of 
F003 and F004, respectively.
Command Control (F003)
The Command Mode selection of F003 establishes the 
primary source of the command input for the ASD. 
However, the Override feature may supersede the 
F003 
setting as indicated in Table 5.
Table 5 on pg. 49 shows the hierarchy of the control 
sources managed by the Override function. The level 
of the control item of the hierarchy is listed from left to 
right, most to least, respectively. As indicated in the table, the Override setting may supersede the 
F003 
setting.
Placing the EOI in the Local mode selects the RS485 2-Wire as the Command Mode control source. 
Local mode operation may be superseded by other Override settings.
Example: With the EOI set to Local, Communication Board input or RS485 4-Wire input will 
supersede EOI control input.
The remaining control sources may be placed into the Override mode using communications.
The source of the Command control signal may be selected by:
•The F003 setting,
• Placing an item from the Command signal source selections in the Override mode via 
communications, or
• Placing the EOI in the Local mode (places only the RS485 [2-Wire] or the RS485 [4-Wire] in the 
Override mode).
Possible Command signal source selections include the following:
• Terminal Board (default),
• EOI Keypad,
• RS485,
• Communication Option Board, or
• F003 setting (is used if no signal sources are in the Override mode).
Note: The Terminal Board is placed in the Override mode for Command functions by 
assigning a discrete terminal to Command Terminal Board Priority and activating 
the terminal by applying 120 VAC. Once activated (Run command required), the 
Terminal Board settings will be used for Override Command control (F, R, Preset 
Speeds, etc.).
(F003) Command Mode
Selection
Terminal Block
efesotomasyon.com -Toshiba inverter,drive,servo,plc