254 ACE-tronics G9 ASD Installation and Operation Manual
Trips/Faults
A Trip is an ASD response to a Fault (though Fault and Trip are sometimes used interchangeably). A
Trip is a safety feature that disables the ASD system in the event that a subsystem of the ASD is
malfunctioning or a parameter setting has been exceeded.
Listed in Table 15 are the Faults that may result in a Trip and the possible causes. When a Trip is
incurred the LCD screen shows the Fault screen and the LED screen displays the active Fault code.
Table 15. ACE-tronics G9 ASD Fault Listing.
LCD Screen LED Screen Possible Causes
Analog Input Loss E-18 V/I signal loss.
ACE G9-120V-PCB failure.
P24 over-current condition.
F633 setting is too high.
Analog Input
Over-Voltage
E-10 Over-voltage at the V/I, RX, or RR input(s).
ASD Overload OL1 Acceleration time is too short.
DC Injection current is too high.
Improper V/f setting.
Motor running during restart.
ASD or the motor is improperly matched to the application.
Autotune Error ETN Autotune readings that are significantly inconsistent with the
configuration information.
A non-3-phase motor is being used.
Incorrect settings at F400 or F413.
Using a motor that has a significantly smaller rating than the ASD.
ASD output cabling is too small, too long, or is being housed in a cable
tray with other cables that are producing an interfering EMF.
Motor is running during the Autotune function.
ETN1 F402 adjustment required (Motor temperature is too high).
F410 adjustment required (Motor Constant 1 improperly set).
ETN2 F412 adjustment required (Motor Constant 3 improperly set).
ETN3 Autotune setting F400 is set to Auto Calculation and there is a
problem with the Motor Constant readings; F405, F406, and F407.
Brake Sequence
Response Error
E-11 F630 is set to a non-zero value.
Braking sequence discrete input and output terminals are not setup
properly.
Communication
Error
ERR5 Communication time out error.
Communication malfunction.
Improper or loose connection.
Improper system settings.