156 ACE-tronics G9 ASD Installation and Operation Manual
Motor Constant 1 (Torque Boost)
Program Motor Vector Motor Model
This parameter sets the primary resistance of the motor. Increasing this value
can prevent a drop in the torque of the motor at low speeds. Increasing this
value excessively can result in nuisance overload tripping.
Direct Access Number F410
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During RunYes
Minimum — 0.0
Maximum — 30.0
Units — %
Motor Constant 2 (No-Load Current)
Program Motor Vector Motor Model
This parameter is used to set the current level required to excite the motor.
Specifying a value that is too high for this parameter may result in hunting
(erratic motor operation).
Direct Access Number F411
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During RunNo
Minimum — 10
Maximum — 90
Units — %
Motor Constant 3 (Leak Inductance)
Program Motor Vector Motor Model
This parameter is used to set the leakage inductance of the motor.
A larger setting here results in higher output torque at high speeds.
Direct Access Number F412
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During RunYes
Minimum — 0
Maximum — 200
Units — %
Motor Constant 4 (Rated Slip)
Program Motor Vector Motor Model
This parameter is used to set the secondary resistance of the motor.
An increase in this parameter setting results in an increase of compensation for
motor slip.
Direct Access Number F413
Parameter Type — Numerical
Factory Default — (ASD-Dependent)
Changeable During RunYes
Minimum — 0.01
Minimum — 25.00
Units — %
Exciting Strengthening Coefficient
Program Special Special Parameters
This parameter is used to increase the magnetic flux of the motor at low-speed.
This feature is useful when increased torque at low speeds is required.
Direct Access Number F415
Parameter Type — Numerical
Factory Default 100
Changeable During RunYes
Minimum — 100
Maximum — 130
Units — %