10 G9000 TOSHIBA SYNC KIT 1000-2000kVA Installation Manual - 200151-001
5 SLAVE UPS Installation Procedures
1. Prior to the installation of the parts, confirm that the AC input breaker,
AC output breaker, Bypass input breaker and DC breaker are turned off.
(De-energize the interior of the UPS.)
2. Then remove the metal cover plates from UPS.
5-1. Install the fuse holder with 2 screws on the upper part of the panel inside bypass module.
5-2. Insert three (3) fuses into the fuse holder.
5-3. Stick the fuse label on the panel near the fuse holder.
5-4. Connect the wire (Part# 3B) between VSAU-48*(CN54) and the fuse holder(M5).
5-5. Connect the field-installed wires (between MASTER and SLAVE UPS) to the fuse holder. Note: wires (qty. 3)
should have 600V insulation and be #16AWG, multi-strand, twisted trio with ring lugs sized for #12 screws.
Figure 5-1: Installation procedures for SLAVE UPS(1000kVA)
Color of wires
A-phase: Yellow
B-phase: Blue
C-phase: White
Field-installed
wires from
MASTER UPS
Wires between
VSAU-48*(CN54)
and fuse holder(M5)
Upper part of bypass cabinet
The connection is for 1000kVA UPS.