G9000 TOSHIBA SYNC KIT 1000-2000kVA Installation Manual - 200151-001 3
2 OVERVIEW
TOSHIBA G9000 Uninterruptible Power Supply Systems (UPS) need a TOSHIBA SYNC KIT whenever two SMS UPSs
are installed in a synchronous operation configuration.
Each TOSHIBA SYNC KIT contains all hardware necessary for one pair of master and slave UPS to operate in a
synchronous configuration. Each additional UPS unit will require another sync kit, if applicable. This manual is
specifically for 1000-2000kVA capacity models of the G9000 Series UPS.
The UPSs must be de-energized when the TOSHIBA SYNC KITs are installed and the
synchronous operation configuration is established between the UPSs.
* PCB revision suffix may be applied.
Figure 2-1: Synchronous Operation Configuration
CAUTION
BYPASS Input
AC Input
INV
CONV
INV
CONV
UPS #B: SLAVE G9000
BYPASS Input
STS
PDU
VSAU-48*
To Load
AC Input
IOAU-19*
TN13
29
30
Jumper
TOSHIBA Sync circuit
Slave
TOSHIBA Sync circuit
Master
Qty. 3 #16AWG, 600V insulation,
multi-strand, twisted trio wire, with ring lugs
for #12 screws.
Field installed by Others