98 H7 ASD Operation Manual
BIN Speed Reference Setpoint #1 (frequency)
Program
Frequency Setting Parameters
Speed Reference
Setpoints
BIN
This parameter is used to set the direction, gain, and bias of the BIN binary input
terminals when these terminals are used as the control input while operating in
the Speed Control mode.
See F228 for further information on this setting.
This parameter sets BIN Speed Reference Setpoint #1 (frequency) and is the
frequency that is associated with the setting of F228.
Direct Access Number F229
Parameter TypeNumerical
Factory Default0.0
Changeable During Run — Yes
Minimum — -80.0
Maximum+80.0
Units — Hz
BIN Speed Reference Setpoint #2 (%)
Program
Frequency Setting Parameters
Speed Reference
Setpoints
BIN
This parameter is used to set the direction, gain, and bias of the BIN binary input
terminals when these terminals are used as the control input while operating in
the Speed Control or the Torque Control mode.
See F228 for further information on this setting.
This parameter sets BIN Reference Setpoint #2 (direction/torque/frequency)
and is entered as 0 to 100% of the BIN binary input word 11111111 (255
D
).
Direct Access Number F230
Parameter TypeNumerical
Factory Default100.0
Changeable During Run — Yes
Minimum — 0.0
Maximum — 100.0
Units — %
BIN Speed Reference Setpoint #2 (frequency)
Program
Frequency Setting Parameters
Speed Reference
Setpoints
BIN
This parameter is used to set the direction, gain, and bias of the BIN binary input
terminals when these terminals are used as the control input while operating in
the Speed Control mode.
See F228 for further information on this setting.
This parameter sets BIN Speed Reference Setpoint #2 (frequency) and is the
frequency that is associated with the setting of F230.
Direct Access Number F231
Parameter TypeNumerical
Factory Default — +80.0
Changeable During Run — Yes
Minimum — -80.0
Maximum+80.0
Units — Hz
BIN Torque Reference Setpoint #1 (%)
Program
Torque Setting Parameters
Setpoints
BIN
This parameter is used to set the direction, gain, and bias of the BIN binary input
terminals when these terminals are used as the control input while operating in
the Torque Control mode.
This is accomplished by establishing an associated V/f output pattern for a given
BIN binary input and motor load.
See F228 for further information on this setting.
This parameter sets BIN Torque Reference Setpoint #1 (%) and is entered as
-250 to +250% of the rated torque.
Direct Access Number F232
Parameter TypeNumerical
Factory Default0.0
Changeable During Run — Yes
Minimum — -250.0
Maximum — +250.0
Units — %